Chapter 10 — OT, IoT and cyber-physical security: orientation

Open, free learning for anyone who wants to protect people and technology. No account is required to read this text or its worked answers.

Permanent link

Public activity · 30d

—Participating browsers

—Page views

—Reading sessions

—Exercise opens

Counts reflect browsers that allowed analytics. A reading session requires 30 seconds on a visible page. Browsers are not people.

Learning outcomes

You will (1) define OT, IoT and cyber-physical systems in NCS terms; (2) describe the refrigeration control loop; (3) name the main guidance documents and who they are for; and (4) explain why safety systems stay outside security changes.

10.1 Three overlapping terms

Operational technology monitors and controls physical processes — here, compressors, evaporator fans and valves. IoT devices are network-connected sensors and actuators — here, the wireless temperature loggers and cameras. A cyber-physical system is the loop of sensing, computing and acting on the physical world. NCS is all three at once.

At NCS the overlap is visible in one room: Freezer-2's probe feeds PLC-R1, while a wireless logger in the same room reports through GW-LOG to the cloud. One is OT, the other IoT, and both describe the same physical temperature, which is what makes the two-probe comparison in Chapter 24 possible.

10.2 The refrigeration loop

A temperature probe in Freezer-2 reports −21 °C; PLC-R1 compares it with the −22 °C setpoint and increases compressor capacity; more refrigerant evaporates, the room cools, and the probe reports again. An attacker who changes the setpoint, falsifies the probe or overrides the compressor command breaks the loop. ATT&CK for ICS T0836 Modify Parameter covers the setpoint case.

Priya's map of this loop, probe TT-F2 → PLC-R1 → compressor C-1 → evaporator → room → TT-F2, adds two independent paths: the wireless logger's second temperature view and the gas-detection panel that trips ventilation without PLC-R1.

10.3 Guidance map

NIST SP 800-82r3 guides OT security programmes for asset owners such as NCS. The IEC 62443 series covers industrial automation and control systems for owners, integrators and product suppliers. NIST IR 8259 describes cybersecurity activities for IoT device manufacturers, and ETSI EN 303 645 sets a baseline for consumer IoT products — useful as a checklist for buying loggers and cameras.

Priya uses EN 303 645 for exactly that purpose: her vendor questionnaire for the loggers asks the 5.1, 5.2, 5.3, 5.5 and 5.8 questions before NCS buys more.

The answers then decide whether a compensating control, such as comparing logger and PLC probes, is needed.

10.4 Safety stays separate

Ammonia gas detection and emergency ventilation are life-safety systems. Security work may observe and report on them, but changes go through the safety owner and the refrigeration engineer, never as a side effect of a firewall project.

At NCS this rule applies directly to Priya's firewall work. When she moved the dock cameras into their own zone, she confirmed with the refrigeration engineer that the gas-detection panel had no network connection the change could affect. If it had, the change would have gone to the safety owner first. Her reports may note that the gas-detection panel trips ventilation without PLC-R1, which reduces several cyber scenarios, but she does not test or reconfigure it.

Worked example (synthetic NCS)

Priya maps the Freezer-2 loop: probe TT-F2 → PLC-R1 → compressor C-1 → evaporator → room → TT-F2. Beside it she notes the independent paths: wireless loggers give a second temperature view to the cloud, and the gas-detection panel trips ventilation without PLC-R1. Both reduce the chance that one compromise hides a problem.

Synthetic case — Northgate Cold Storage. Tag names are invented.

Errors and limits

Consumer IoT standards do not automatically apply to industrial devices; use them as reference questions. Loop diagrams simplify; real systems have cascades and interlocks.

Exercises

  • EX028 — Three attack points on the Freezer-2 loop. Name one per element: sensor, controller, actuator.
    Show marking criteria
    Rubric: 3 = three plausible points; 2 = two; 1 = one; 0 = none.
  • EX029 — Choosing a buying checklist. Which document would you use to write purchase questions for new temperature loggers?
    Show marking criteria
    Rubric: 3 = ETSI EN 303 645 (or NIST IR 8259 for manufacturer activities) with reason; 2 = name only; 1 = SP 800-82 only; 0 = none.
  • EX030 — Why loggers help integrity. Explain how the cloud loggers reduce the impact of a falsified TT-F2 reading.
    Show marking criteria
    Rubric: 3 = independent measurement path reveals disagreement; 2 = partial; 1 = vague; 0 = none.

Synthesis

Orientation means seeing the physical loop, knowing which guidance fits which role, and keeping safety systems out of security side effects.

Continue studying — chapter 10 of 30

← Chapter 09 (draft) · Course chapter index · Chapter 11 (draft) →

Practice the exercises

Open a prompt, write your response, then compare it with the worked answer. Five-choice practice appears where a reviewed question is available.

EX028

Opens in 30 days: — · browsers: —

Checking for a reviewed five-choice question…

EX029

Opens in 30 days: — · browsers: —

Checking for a reviewed five-choice question…

EX030

Opens in 30 days: — · browsers: —

Checking for a reviewed five-choice question…

Worked answers

EX028. Sensor: falsify or disconnect TT-F2 so it reads colder than reality. Controller: change PLC-R1's Freezer-2 setpoint (T0836). Actuator: force compressor C-1 off through a manual override or output manipulation.

EX029. ETSI EN 303 645: its provisions (no universal default passwords, vulnerability disclosure, updatable software, secure communication) translate directly into purchase questions; NIST IR 8259 is a good complement for asking what the manufacturer does.

EX030. The loggers measure Freezer-2 independently and report by a different path; if TT-F2 is falsified to read −22 °C while the room warms, the logger data will disagree and reveal the problem.