[Learning outcomes]
    |
    v
[2.1 The scan cycle]
    |
    v
[2.2 PLC versus server]
    |
    v
[2.3 What lives in firmware]
    |
    v
[Synthesis]
    |
    v
[Worked example] --> [Exercise EX004]

Learning outcomes

You will (1) describe the layers of a programmable logic controller from I/O card to scan cycle; (2) contrast a PLC with a general-purpose server; (3) explain why deterministic timing is a security property in OT; and (4) list what a firmware image contains.

2.1 The scan cycle

A PLC repeatedly reads inputs, executes logic, writes outputs and services communications. At LDHP the boiler PLC-H completes this loop every 20 ms. If communication handling grows — for example because a misconfigured historian polls 400 registers every 50 ms — the scan time stretches and the watchdog may trip the controller into a safe stop. A denial of service in OT can therefore arrive as ordinary traffic that is simply too much.

Maya met this in her second week: a dashboard project asked for "all tags, every scan". Converted into scan time, that request would have loaded PLC-H's communication handling on every 20 ms cycle, so she recommended reading the historian instead.

2.2 PLC versus server

A server is designed to run many programs, accept updates and recover by reboot. A PLC is designed to run one program for years, often with no user accounts, limited logging and firmware that the vendor signs (or, in older models, does not sign). Rebooting a server is routine; restarting a controller in a running boiler house requires a work permit, operator presence and a plan to hold the process safe.

For PLC-H this means a firmware fix cannot simply be applied on a Tuesday afternoon: it needs the monthly four-hour window, a work permit and the shift lead present.

2.3 What lives in firmware

Firmware bundles a real-time operating system, protocol stacks, the runtime that executes ladder or structured text, and a bootloader. Security consequences follow: a protocol stack bug can affect every program on the device, and an unsigned update path lets anyone who reaches the engineering port replace the runtime. NIST SP 800-82r3 treats firmware integrity and controlled program download as core OT practices.

For PLC-H, the practical question is who can reach the engineering port: if EWS-1 is the only host that can, protecting EWS-1 protects the runtime; if the office VLAN can reach port 502 as well, the firmware's signing behaviour becomes the last barrier.

Worked example (synthetic LDHP)

PLC-H has a 20 ms target scan and a 100 ms watchdog. Logic takes 9 ms, I/O 4 ms, and each Modbus request costs 0.6 ms to service. With 10 requests per scan the cycle is 9 + 4 + 6 = 19 ms. If a new dashboard adds 30 requests per scan, the cycle becomes 37 ms: still under the watchdog, but the 20 ms timing that tuned loops expect is lost and control quality degrades before any alarm fires.

Synthetic case — Lakeside District Heating Plant. Maya finds a dashboard project asking for "all tags, every scan". She converts the request into scan milliseconds and recommends polling the historian, not the controller.

Errors and limits

Vendor scan models differ; some service communications in a separate task. Never measure scan impact by loading a production controller — use a bench unit or the vendor's figures.

Exercises

Synthesis

A controller is a timed machine first and a computer second; its security starts with respecting the scan cycle and controlling what may be loaded onto it.

Continue studying — chapter 02 of 40

← Chapter 01 (draft) · Course chapter index · Chapter 03 (draft) →

Worked answers

EX004. 9 + 4 = 13 ms leaves 7 ms; 7 / 0.6 = 11.67, so at most 11 requests per scan (11 × 0.6 = 6.6 ms → 19.6 ms).

EX005. (1) Rebooting to clear a fault → schedule a controlled stop with operators holding the process safe. (2) Installing updates immediately → stage firmware on a bench unit and deploy in a maintenance window with rollback. Disabling services ad hoc or running scanners are also acceptable examples.

EX006. The protocol stack is shared by the whole device and parses network input before any user logic executes, so a flaw there can crash or control the controller regardless of which program is loaded; a ladder bug only affects the function that rung implements.